Ihab Saad – Subpart F Fire

Ihab Saad
AI: Summary ©
The speakers discuss the potential risks of fire in construction sites, including the use of various fire protection equipment and the importance of preventing damage to buildings. They emphasize the need for electrical wiring and equipment to prevent fire hazard and damage to electrical wiring. The speakers also discuss the proper construction and fire extinguishers for preventing damage to electrical wiring, the use of storage facilities for fire hazards, and the importance of preventing ignition in heating devices. The speakers stress the importance of preventing fire from ignition and ensuring proper protection for workers and employees.
AI: Transcript ©
00:00:03 --> 00:00:06

Welcome to another safety class, and today we're going to talk

00:00:06 --> 00:00:09

about subpart F, which is fire protection and prevention.

00:00:10 --> 00:00:13

Definitely, fires are one of the major hazards on construction

00:00:13 --> 00:00:16

sites. So today we're going to talk about what could be the major

00:00:17 --> 00:00:22

sources of that fire and how to protect against any fires on

00:00:22 --> 00:00:23

construction sites.

00:00:25 --> 00:00:29

So that's just an example to show here that we have some combustible

00:00:30 --> 00:00:34

fuels, which in this case is oxygen tanks. If fire reaches

00:00:34 --> 00:00:37

these tanks, which is very close here, that can cause a major

00:00:37 --> 00:00:40

explosion and a huge fire,

00:00:42 --> 00:00:46

the most frequently cited violations when it comes to

00:00:47 --> 00:00:51

to fire. That was actually in the year 2004 which is pretty much the

00:00:51 --> 00:00:52

same for every year

00:00:54 --> 00:00:56

150 c1 I

00:00:57 --> 00:01:01

fire extinguishes for every 3000 square feet of building area not

00:01:01 --> 00:01:02

existing.

00:01:03 --> 00:01:10

150 c1, four, extinguishers on each floor are not existing. 153

00:01:11 --> 00:01:12

Oh,

00:01:13 --> 00:01:18

liquid petroleum gas systems, Petro protection from vehicular

00:01:18 --> 00:01:23

traffic. 150 a, one five, the non existence of a fire protection

00:01:23 --> 00:01:30

program, and 150 c1, six extinguishers within 50 feet of

00:01:30 --> 00:01:34

flammables. So these are the major violations when it relates to

00:01:35 --> 00:01:35

fire.

00:01:37 --> 00:01:41

Let's first of all identify a few things. The first definition is

00:01:41 --> 00:01:45

about what is flammable. Flammable is any material capable of being

00:01:45 --> 00:01:50

easily ignited, burning intent intensely or having a rapid rate

00:01:50 --> 00:01:52

of flame spread.

00:01:53 --> 00:01:58

Flammable liquids are liquids having a flash point, which is the

00:01:58 --> 00:02:03

point of ignition below 140 degrees Fahrenheit and a vapor

00:02:03 --> 00:02:08

pressure not exceeding 40 pounds per square inch. So these are the

00:02:08 --> 00:02:09

flammable liquids.

00:02:11 --> 00:02:14

Another definition is a safety can, because we're going to talk

00:02:14 --> 00:02:17

about storage in safety can. So what's a safety can? It's an

00:02:17 --> 00:02:22

approved closed container of not more than five gallon capacity,

00:02:22 --> 00:02:28

having a flash arresting screen, spring closing lid and spout cover

00:02:28 --> 00:02:33

designed so it will safely relieve internal pressure when exposed to

00:02:33 --> 00:02:37

fire, because if the pressure keeps building Inside, it's going

00:02:37 --> 00:02:37

to explode.

00:02:40 --> 00:02:41

These are samples of

00:02:43 --> 00:02:48

these safety cans. And as you can see, it's labeled as a safety can,

00:02:48 --> 00:02:52

and the liquid inside is a flammable liquid. This one here is

00:02:52 --> 00:02:55

a regular gas, and so on. So they are going to be labeled on the

00:02:55 --> 00:02:56

outside as well.

00:02:58 --> 00:03:00

That's another example of a safety can

00:03:03 --> 00:03:06

these are definitely not considered to be safety cans

00:03:06 --> 00:03:10

because they do not satisfy the previous conditions. So you cannot

00:03:10 --> 00:03:12

store flammable liquids in these

00:03:15 --> 00:03:21

that's another example of an non approved container for flammable

00:03:21 --> 00:03:24

liquids. In this case, actually, it's covered, even not with the

00:03:24 --> 00:03:28

cover, but with the rag for the cap. So that's a double whammy.

00:03:31 --> 00:03:34

General requirements when it comes to fire protection, the employer

00:03:34 --> 00:03:37

must develop the fire protection program to be followed through

00:03:37 --> 00:03:40

construction and provide all equipment as required for

00:03:40 --> 00:03:43

firefighting, we're going to talk about the different kinds of

00:03:43 --> 00:03:47

equipment that are going to be used in case of building under

00:03:47 --> 00:03:49

construction or a permanent construction, or whatever

00:03:51 --> 00:03:55

water supply a temporary Of course, as we know, the easiest

00:03:55 --> 00:03:59

way to put off fires is using water so a temporary or permanent

00:03:59 --> 00:04:04

water supply of sufficient volume, duration and pressure must be made

00:04:04 --> 00:04:07

available as soon as combustible materials accumulate.

00:04:08 --> 00:04:11

Where underground water mains are to be provided, they must be

00:04:11 --> 00:04:15

installed and available as soon as practical at the very beginning of

00:04:15 --> 00:04:19

the construction project. So usually when you see immediately

00:04:19 --> 00:04:23

after the excavation, we have the infrastructure, which includes the

00:04:23 --> 00:04:26

water pipes and the water mains and sewage lines and so on and so

00:04:26 --> 00:04:27

forth.

00:04:30 --> 00:04:33

Here's an example on the installation of water main as and

00:04:33 --> 00:04:36

as you can see, that's at the very beginning phases of construction.

00:04:40 --> 00:04:45

Water Supply stand pipes in all structures where standpipes are

00:04:45 --> 00:04:49

required, they must be maintained as construction progresses in such

00:04:49 --> 00:04:52

a manner that they are always ready for fire protection use. So

00:04:52 --> 00:04:56

these are going to be dedicated for fire protection. Standpipes

00:04:56 --> 00:04:59

must be provided with the Siamese Fire Department Connect.

00:05:00 --> 00:05:03

Action on the outside of the structure at the street level and

00:05:03 --> 00:05:09

conspicuously marked. So. This is an example of the Siamese Fire

00:05:09 --> 00:05:13

Department connection, which is has more than one outlet, as you

00:05:13 --> 00:05:17

can see, and they have to be conspicuously marked, which means

00:05:17 --> 00:05:21

marked in a very obvious place, so that no one is going to search for

00:05:21 --> 00:05:23

them, or they can be hidden.

00:05:24 --> 00:05:27

So here's an example, fire department, departments, 10, five

00:05:27 --> 00:05:29

connection. It's very clear with a sign

00:05:31 --> 00:05:35

fire cutoffs. Now, in case of a fire, we want to limit the spread

00:05:35 --> 00:05:39

of that fire, basically until we get some external support, or

00:05:39 --> 00:05:42

someone calls the fire department and things like that. So when

00:05:42 --> 00:05:45

talking about walls and doors that are going to contain that fire,

00:05:46 --> 00:05:51

fire walls and exit stairways must be given construction priority. So

00:05:51 --> 00:05:54

you're going to have fire rated dry walls, for example, or fire

00:05:54 --> 00:05:59

rated masonry walls or block walls, things like that. Fire

00:05:59 --> 00:06:04

doors must be hung on openings as soon as practical again, to

00:06:04 --> 00:06:07

isolate that fire and keep it contained within that room. Fire

00:06:07 --> 00:06:11

cutoffs must be retained in buildings undergoing alterations

00:06:11 --> 00:06:15

or demolition until operations require their removal. These

00:06:15 --> 00:06:18

include things like sprinklers, for example, if you're going to

00:06:19 --> 00:06:22

demolish a building or you're going to alter the internal use of

00:06:22 --> 00:06:26

the building, you should keep the sprinklers until the last possible

00:06:26 --> 00:06:30

moment, so that in case a fire erupts, at least you're gonna have

00:06:30 --> 00:06:32

the means to put it off.

00:06:35 --> 00:06:39

Portable firefighting equipment are usually extinguishers, which

00:06:39 --> 00:06:44

must be placed as follows, one to a extinguisher for every three

00:06:44 --> 00:06:49

3000 square feet of floor, space, travel distance not to exceed 100

00:06:49 --> 00:06:52

feet. So that anyone from any point on that floor,

00:06:53 --> 00:06:56

anyone trying to reach that fire extinguisher, are not going to

00:06:56 --> 00:07:01

travel more than 100 feet, at least one per floor and one by

00:07:01 --> 00:07:05

each stairwell. So these are the requirements for the portable

00:07:05 --> 00:07:06

extinguishers.

00:07:08 --> 00:07:11

The alternative to a two way extinguisher is going to be a 55

00:07:11 --> 00:07:16

gallon drum of water with two fire pails. So that's an alternative,

00:07:16 --> 00:07:21

or a half inch garden hose, not longer than 100 feet, because

00:07:21 --> 00:07:25

otherwise it can get tangled and get knots with nozzle capable of

00:07:25 --> 00:07:29

discharging five gallons per minute, so allowing for a quick

00:07:29 --> 00:07:34

discharge of water, the hoses must be located on racks or reefs again

00:07:34 --> 00:07:38

to prevent the puncture to the hoses or the disconnection or the

00:07:38 --> 00:07:40

tangling and knotting and so on.

00:07:45 --> 00:07:48

Another portable firefighting equipment would be a 10 B

00:07:48 --> 00:07:54

extinguisher, which must be within 50 feet of five gallons of

00:07:54 --> 00:07:57

flammable liquid or gas. We're going to talk about the A and the

00:07:57 --> 00:08:01

B and so on in just a couple of minutes. So a 10 B, extinguisher

00:08:01 --> 00:08:05

which is going to be suitable for flammable liquids or gasses, has

00:08:05 --> 00:08:09

to be placed within 50 feet of any five gallons containers.

00:08:10 --> 00:08:17

Extinguishers must be inspected and maintained per NF PA, which is

00:08:17 --> 00:08:19

a National Fire Protection Agency.

00:08:22 --> 00:08:27

Here we have a B, actually it's a b and c, but the C has been

00:08:28 --> 00:08:33

torn from or erased from, from that distinguisher. So it shows

00:08:33 --> 00:08:37

what kind of fires it can resist, and it shows its capacity when it

00:08:37 --> 00:08:41

was inspected, who inspected it, and so on and so forth. So it

00:08:41 --> 00:08:42

shows that it's ready for use.

00:08:44 --> 00:08:48

It must be conspicuously located. So again, here you can clearly see

00:08:48 --> 00:08:49

it on site

00:08:52 --> 00:08:55

and easily accessible on any floor, as we mentioned before.

00:08:59 --> 00:09:01

Now to talk about the different types of fire, we have four

00:09:01 --> 00:09:05

different categories of four different groups of fires, which

00:09:05 --> 00:09:11

are A, B, C and D, the higher the latter, the more serious the fire

00:09:11 --> 00:09:17

and the hotter that fire. So type A is lower than b, b is lower than

00:09:17 --> 00:09:20

C, C is lower than d, d is the highest one

00:09:21 --> 00:09:26

that classification, A is for wood, paper or trash, which is

00:09:26 --> 00:09:30

most common, but can be easily extinguished. Its burning

00:09:31 --> 00:09:35

temperature is not going to be that high. B is for flammable

00:09:35 --> 00:09:38

liquids. That's why we mentioned that you're going to have it near

00:09:38 --> 00:09:43

the containers, the five gallon containers less than 50 feet. C is

00:09:43 --> 00:09:45

electrical equipment that's going to be burning at a higher

00:09:45 --> 00:09:49

temperature, and D is combustible metals that's going to be the

00:09:49 --> 00:09:51

highest temperature, and it's going to be the longest lasting

00:09:52 --> 00:09:54

and the hardest to extinguish, basically.

00:09:56 --> 00:09:59

And as you can notice, each one of them, in addition to the letter,

00:09:59 --> 00:09:59

has a.

00:10:00 --> 00:10:05

Symbol. So the A is in a triangle, the B is in a square, the C this

00:10:05 --> 00:10:08

in a circle, and the D is in a star.

00:10:11 --> 00:10:15

The sizing of the extinguishers, portable extinguishers are rated

00:10:15 --> 00:10:19

for the size of fire they can handle. This rating is a number

00:10:19 --> 00:10:25

from one to 40 for Class A fires, and one to 640 for Class B fires.

00:10:26 --> 00:10:30

The larger the number, the larger the fire the extinguisher can put

00:10:30 --> 00:10:35

out. So the higher, the stronger that extinguisher.

00:10:38 --> 00:10:42

This extinguisher, for example, can work for three types, A, B and

00:10:42 --> 00:10:44

C. So this is a multipurpose extinguisher.

00:10:46 --> 00:10:48

This one is only for B and C.

00:10:50 --> 00:10:54

For B and C, it can also cover a, but again, it's going to be

00:10:54 --> 00:10:58

probably too expensive to use regularly for A, because A can be

00:10:58 --> 00:10:59

extinguished much easier than that.

00:11:01 --> 00:11:05

How to properly use a fire extinguisher. Always use the pass

00:11:05 --> 00:11:10

system. Remember that pass. Pass stands for the P is, pull the a

00:11:10 --> 00:11:14

is, aim. We're talking about the extinguisher, pull the pin, aim

00:11:14 --> 00:11:19

the nozzle, squeeze and then sweep across the base of the fire to

00:11:19 --> 00:11:20

extinguish that fire.

00:11:21 --> 00:11:24

So the first step is to pull the pin. This allows you to discharge

00:11:24 --> 00:11:25

the extinguisher.

00:11:26 --> 00:11:31

That pin is a safety measure, just to so that it wouldn't discharge

00:11:32 --> 00:11:33

by accident.

00:11:34 --> 00:11:35

Aim, aim

00:11:36 --> 00:11:39

the extinguisher at the base of the fire, aiming that the flames

00:11:39 --> 00:11:42

would not put out the fire, but the base of the fire, that's where

00:11:42 --> 00:11:43

the ignition is,

00:11:44 --> 00:11:48

squeeze the handle. This would release the extinguishing agent,

00:11:48 --> 00:11:50

whether it's powder, foam or water, whatever,

00:11:51 --> 00:11:55

and sweep from side to side with the extinguishing agent until the

00:11:55 --> 00:11:59

fire is out. So to cover across the base of that fire

00:12:02 --> 00:12:05

during demolition or alteration, as we just mentioned, sprinklers

00:12:05 --> 00:12:08

must be retained in service as long as reasonable. New

00:12:08 --> 00:12:12

construction utilizing automatic sprinklers must must follow the

00:12:12 --> 00:12:17

work and be placed in service as soon as practical. So for they're

00:12:17 --> 00:12:22

basically the last out the first in. So once you are dismantling or

00:12:22 --> 00:12:26

altering or demolishing, they stay for as long as possible, and when

00:12:26 --> 00:12:29

you are building a new then they are installed as soon as possible.

00:12:32 --> 00:12:35

Alarm devices. An alarm system must be established by the

00:12:35 --> 00:12:40

employer that alerts employees and the fire department. The alarm

00:12:40 --> 00:12:45

system can be phone, siren, radio, air horns, etc, and the aligned

00:12:45 --> 00:12:49

alarm system must be posted at phones and job entrances so people

00:12:49 --> 00:12:53

would know where that alarm system is, so that they can notify

00:12:53 --> 00:12:55

everyone as soon as the fire alarms

00:12:57 --> 00:13:01

electrical wiring and equipment. When we talked about electrical

00:13:01 --> 00:13:03

work, we mentioned that fire is going to be one of the major

00:13:03 --> 00:13:06

hazards in electrical work. So electrical wiring equipment for

00:13:06 --> 00:13:10

light, heat and power must be installed per subpart K, which is

00:13:10 --> 00:13:14

electrical. Gas powered equipment must point exhaust away from

00:13:14 --> 00:13:18

combustible material, so that the heat from that exhaust might not

00:13:18 --> 00:13:23

cause ignition to that material. Smoking must be prohibited in work

00:13:23 --> 00:13:26

areas which may pose a fire hazard, so it's a better policy to

00:13:26 --> 00:13:32

have zero smoking tolerance on construction sites. Now look at

00:13:32 --> 00:13:38

this. He just chose the no smoking sign to start smoking underneath

00:13:38 --> 00:13:38

it,

00:13:41 --> 00:13:45

no temporary building may be erected where it would block or

00:13:45 --> 00:13:49

hinder an exit, because, again, in case of a fire, you want to have a

00:13:49 --> 00:13:52

safe exit for those who are inside the building. Temporary buildings

00:13:52 --> 00:13:56

must be erected at least 10 feet from other structures, again to

00:13:56 --> 00:14:00

allow for enough space for people to get out of the building. In the

00:14:00 --> 00:14:04

case of panic, it must be constructed of non combustible

00:14:04 --> 00:14:08

materials or have a fire resistance of not less than one

00:14:08 --> 00:14:12

hour, so it can resist in case it gets on fire before collapsing,

00:14:12 --> 00:14:14

it's going to resist the spread of that fire for at least an hour.

00:14:18 --> 00:14:22

In case of open yard storage, combustibles must not be stacked

00:14:22 --> 00:14:26

more than 20 feet high. So if you have any combustible material,

00:14:26 --> 00:14:29

you're gonna stack it on site, in open yard storage not higher than

00:14:29 --> 00:14:34

20 feet storage area must be kept clear of weeds, trash, or any

00:14:34 --> 00:14:38

other combustibles that can ignite or can help with the ignition. So

00:14:38 --> 00:14:43

you want to avoid that driveways must be at least 15 feet wide and

00:14:43 --> 00:14:46

free of debris to accommodate travel of fire trucks, because you

00:14:46 --> 00:14:49

know the fire trucks are much wider than regular vehicles, so

00:14:49 --> 00:14:53

you want to allow for at least 15 feet wide access. You.

00:15:00 --> 00:15:03

The entire storage site must be kept free of accumulation of

00:15:03 --> 00:15:08

unnecessary combustible materials to try to limit the occurrence of

00:15:08 --> 00:15:12

fire as much as possible. No combustible material may be stored

00:15:12 --> 00:15:15

outdoors within 10 feet of a building or structure, because, in

00:15:15 --> 00:15:18

case, people are trying to get out of the building, they do not need

00:15:18 --> 00:15:22

to be exposed to an additional hazard of fire facing them, a

00:15:22 --> 00:15:26

portable fire extinguisher, not less than two A must be located

00:15:26 --> 00:15:30

within 100 feet. So that's in case of open yard storage.

00:15:31 --> 00:15:35

For indoor storage, all materials must be stored, handled and piled,

00:15:36 --> 00:15:40

with due regard to their fire characteristics, non combustible

00:15:40 --> 00:15:44

materials which may create a fire hazard must be segregated by a

00:15:44 --> 00:15:48

barrier with a fire resistance of at least one hour. So the minimum

00:15:48 --> 00:15:51

fire resistance in this case to enclose the fire is going to be at

00:15:51 --> 00:15:55

least one hour, clearance of at least 36 inches must be maintained

00:15:55 --> 00:15:59

between stored materials and sprinkler deflectors, again to

00:15:59 --> 00:16:04

allow for the sprinklers to work properly and to spread to the

00:16:04 --> 00:16:05

required area.

00:16:09 --> 00:16:12

Maintain clearance around lights and heating units to prevent

00:16:12 --> 00:16:17

ignition of combustibles. So do not store the combustible material

00:16:17 --> 00:16:21

too close to a source of heat or source of fire where it can cause

00:16:21 --> 00:16:26

that ignition, adequate clearance must be maintained around fire

00:16:26 --> 00:16:28

doors, again, because the fire doors are going to be used to

00:16:29 --> 00:16:32

enclose the fire in case someone is inside, they need to get out.

00:16:32 --> 00:16:37

So you need to have easy and free access in and out of that room

00:16:39 --> 00:16:43

for Flammable and combustible liquids on the approved containers

00:16:43 --> 00:16:46

and tanks, which are portable tanks that we're talking about,

00:16:46 --> 00:16:50

are to be used. It cannot be stored at exits, stairs or

00:16:50 --> 00:16:53

passageways, because, again, that defeats the purpose of an exit

00:16:53 --> 00:16:57

point in case of a fire. These, by themselves, are a big fire hazard,

00:16:57 --> 00:17:01

so you want to eliminate them, or keep them away from the exits and

00:17:01 --> 00:17:02

the doors and the stairs

00:17:06 --> 00:17:10

here are, for example, flammable stored in a stairwell with no fire

00:17:10 --> 00:17:12

extinguisher in the area. That's a big violation

00:17:16 --> 00:17:20

for the storage of these Flammable and combustible liquids, no more

00:17:20 --> 00:17:24

than 25 gallons of flammable or combustible liquids may be stored

00:17:24 --> 00:17:28

in a room outside of an approved storage cabinet. So they have you

00:17:28 --> 00:17:33

can have more than 25 gallons, but inside the storage cabinet, no

00:17:33 --> 00:17:38

more than 60 gallons of flammable, of flammable or 120 gallons of

00:17:38 --> 00:17:41

combustible liquids can be stored in any one storage cabinet. So

00:17:41 --> 00:17:45

even if you're gonna have a storage cabinet to contain this

00:17:45 --> 00:17:50

combustible or flammable material, it should not contain more than 60

00:17:50 --> 00:17:53

gallons of flammable or 120 of combustible.

00:17:54 --> 00:17:58

Now, which one is easier to ignite, the flammable or the

00:17:58 --> 00:18:02

combustible? Obviously the flammable. That's why we have a

00:18:02 --> 00:18:02

lower limit.

00:18:05 --> 00:18:09

So here, for example, we have improper fuel storage in a job

00:18:09 --> 00:18:14

office trailer. First of all, it's close to a heat source, not proper

00:18:15 --> 00:18:20

containers stacked improperly, and the amount is not inside a

00:18:20 --> 00:18:21

cabinet, as we just mentioned

00:18:24 --> 00:18:28

here, we have them inside a room, and we have no smoking sign. We

00:18:28 --> 00:18:32

have the fire extinguisher. We have a fire rated door, and we

00:18:32 --> 00:18:35

have all signs of warning on that on that door,

00:18:39 --> 00:18:44

no more than 1100 gallons may be stored in any one pile or area of

00:18:44 --> 00:18:49

combustible or flammable liquids. Piles must be separated by five

00:18:49 --> 00:18:53

foot clearance again to allow for access between these piles, to

00:18:53 --> 00:18:58

prevent the spread of that fire, piles must not be closer than 20

00:18:58 --> 00:19:02

feet to any building again to allow for ease of a safety zone or

00:19:02 --> 00:19:06

access zone between the building and the storage area for these

00:19:06 --> 00:19:08

Flammable and combustible liquids.

00:19:09 --> 00:19:11

Storage area must be guarded,

00:19:12 --> 00:19:17

must be graded, to divert spills away from buildings or other

00:19:17 --> 00:19:22

exposures, so again, to allow for the natural flow of these liquids

00:19:22 --> 00:19:26

away from the building or surrounded by a curb or earth dike

00:19:26 --> 00:19:31

at least 12 inches high, again, to prevent the spread of the leakage

00:19:31 --> 00:19:35

of that combustible or flammable liquid, storage areas must be,

00:19:35 --> 00:19:40

must be kept, must keep, must be kept free of weeds, debris and

00:19:40 --> 00:19:43

other combustibles. There's a missing B here, but anyway,

00:19:43 --> 00:19:46

storage areas must be kept free of weeds, debris and other

00:19:46 --> 00:19:49

combustibles that can help with the ignition.

00:19:51 --> 00:19:55

Storage areas in buildings must have a 20 B fire extinguisher, so

00:19:55 --> 00:19:57

Grade B at least

00:19:58 --> 00:19:59

outside the room, but not more than two.

00:20:00 --> 00:20:05

Feet from the door. Again, for ease of access, outside storage

00:20:05 --> 00:20:10

areas must have a 20 B fire extinguisher, not less than 25

00:20:10 --> 00:20:15

feet nor more than 75 feet away from the area. You don't want to

00:20:15 --> 00:20:18

keep it too close, and you don't want to keep it too far away from

00:20:18 --> 00:20:19

the area as well.

00:20:22 --> 00:20:26

When transferring liquids from one container to another, the

00:20:26 --> 00:20:31

containers must be electrically bonded to prevent any sparks that

00:20:31 --> 00:20:35

might allow for ignition. Equipment must be shut off during

00:20:35 --> 00:20:42

refueling. So if you're going to fuel a a any piece of equipment,

00:20:42 --> 00:20:45

whether portable or heavy piece of equipment, it must be shut off

00:20:46 --> 00:20:50

during that refueling. Flammable liquids must only be used when at

00:20:50 --> 00:20:55

least 50 feet away from open flames and other sources of

00:20:55 --> 00:20:58

ignition. So if you're going to do that refueling again, you have to

00:20:58 --> 00:21:02

be away at least 50 feet from an open flame or other source of

00:21:02 --> 00:21:02

English

00:21:04 --> 00:21:10

service and fueling areas must have at least a 20 BC extinguisher

00:21:10 --> 00:21:14

within 75 feet of pump. So you're going to see that, for example, in

00:21:14 --> 00:21:19

gas stations, area around tank must have proper berm or drainage

00:21:19 --> 00:21:25

to allow for the fluid to drain away from the equipment tank to be

00:21:25 --> 00:21:30

labeled, identifying contents and hazards, no smoking or open flames

00:21:30 --> 00:21:34

and fueling areas, these are all areas where there could be some

00:21:34 --> 00:21:38

violations that can cause fires. Here, for example, we have a large

00:21:38 --> 00:21:44

fuel tank with no proper berm, no signage, or no fire extinguisher.

00:21:44 --> 00:21:45

So that's a big,

00:21:46 --> 00:21:54

big problem. This one here has a berm surrounding it. It has a fire

00:21:54 --> 00:21:58

extinguisher. It has the sign, danger, no smoking. So this is the

00:21:58 --> 00:22:00

proper construction of that tank.

00:22:02 --> 00:22:07

And work liquefied petroleum gas or LPG, storage inside buildings

00:22:07 --> 00:22:10

is prohibited, so you cannot store it. You should not store it inside

00:22:10 --> 00:22:14

buildings, because it can explode. Storage outside of buildings, it

00:22:14 --> 00:22:18

has to be done according to the following table here, depending on

00:22:18 --> 00:22:23

the quantity, how far from the building it should be. So if it's

00:22:23 --> 00:22:26

500 pounds or less, it can be very close to the building. Distance in

00:22:26 --> 00:22:32

feet, no distance, 501 to 6000 pounds, at least 10 feet. 6001

00:22:33 --> 00:22:37

pounds to 10,000 pounds at least 20 feet. And over 10,000 pounds at

00:22:37 --> 00:22:39

least 25 feet away from the building.

00:22:42 --> 00:22:48

So here, for example, we have a proper storage outside of the

00:22:48 --> 00:22:52

building with a proper clearing space. This is, this is a

00:22:52 --> 00:22:55

temporary storage, by the way. It's not a permanent building, and

00:22:55 --> 00:22:59

it has the all the warnings outside so, and it's properly

00:22:59 --> 00:23:05

locked to prevent any inadvertent use of these tanks

00:23:08 --> 00:23:11

for temporary heating devices if we're working in a cold weather,

00:23:11 --> 00:23:16

we need to create a nice work environment for the employees. So

00:23:16 --> 00:23:21

we're going to provide space heaters or heating devices so

00:23:21 --> 00:23:24

fresh air must be supplied in adequate amounts to maintain the

00:23:24 --> 00:23:27

health and safety of employees, because many of these heating

00:23:27 --> 00:23:34

devices have used gas or combustible fuels, and the fumes

00:23:34 --> 00:23:38

from these fuels may be toxic, so you want to have renewed fresh air

00:23:38 --> 00:23:43

in The area. Flammable liquid fired heaters are to be equipped

00:23:43 --> 00:23:46

with the fuel shut off control to stop fuel in the event of flame

00:23:46 --> 00:23:51

failure. If the flame is extinguished and the fuel keeps on

00:23:51 --> 00:23:56

being emitted, then can that can cause a risk of asphyxiation

00:23:58 --> 00:24:01

when heaters are used in confined spaces, sufficient ventilation

00:24:01 --> 00:24:06

must be provided, again, because of these fumes and gasses, if

00:24:06 --> 00:24:10

you're going to use solid fuel salamanders, they are prohibited

00:24:10 --> 00:24:13

in buildings and on scaffolds. This is an example of a solid fuel

00:24:13 --> 00:24:18

Salamander. These are not allowed inside buildings or on scaffolds.

00:24:21 --> 00:24:25

Heat is not suitable for use on wood floors, must stress on

00:24:25 --> 00:24:29

suitable heat insulating material. The material must extend beyond

00:24:29 --> 00:24:34

the heater, two feet or more in all directions to create a source

00:24:34 --> 00:24:38

of insulation between the heater, the heater and the wood floor,

00:24:38 --> 00:24:41

which is flammable by itself.

00:24:43 --> 00:24:48

When heaters are used near tarps, Canvas or similar coverings, they

00:24:48 --> 00:24:52

must be located at least 10 feet from the coverings, because all of

00:24:52 --> 00:24:56

these coverings can ignite. So you want to avoid that. Coverings must

00:24:56 --> 00:24:59

be securely fastened to prevent ignition due to.

00:25:00 --> 00:25:05

Wind, so that the flapping of the tarp or the Canvas can get it

00:25:05 --> 00:25:08

closer than the 10 feet. So you want to secure them in place.

00:25:16 --> 00:25:19

If we look at this picture, we're going to find several violations.

00:25:19 --> 00:25:26

First of all, improper gas cans canisters. These are okay, but

00:25:26 --> 00:25:32

these ones are not a heat source and so on, and they're not

00:25:32 --> 00:25:36

properly stored. So that's a big violation here,

00:25:37 --> 00:25:42

another violation here, we have a coverall stored on top of gas

00:25:43 --> 00:25:49

tank. So this is flammable. We have here curtains, it seems like

00:25:49 --> 00:25:52

curtains or something like that, that probably could also be

00:25:52 --> 00:25:56

flammable. So that's not and some other clothing here. So that's not

00:25:56 --> 00:25:57

the proper storage.

00:25:59 --> 00:26:03

Welding fires one of the most frequent causes of construction

00:26:03 --> 00:26:07

fires is the use of welding or cutting torches. The issue is that

00:26:07 --> 00:26:10

there's going to be some residual heat. Even after you're done with

00:26:10 --> 00:26:14

the welding, the method itself might still be hot. It's

00:26:14 --> 00:26:17

imperative that sparks not be allowed to fall on combustible

00:26:17 --> 00:26:21

materials. That's sparks are one source of the ignition. Use fire

00:26:21 --> 00:26:25

retarder tarps or blankets when combustibles cannot be removed.

00:26:28 --> 00:26:31

And here we're gonna need we're gonna talk about a hot work

00:26:31 --> 00:26:34

permit, which is a permit that's needed for certain kinds of work,

00:26:34 --> 00:26:38

although not required. Many companies require hot work permit

00:26:38 --> 00:26:42

for any operation using flames or producing sparks, requires

00:26:42 --> 00:26:47

management authorization before hot work may commence, and the

00:26:47 --> 00:26:50

permit should include inspecting and isolating combustible

00:26:50 --> 00:26:54

materials and establishing a fire watch. Would have gone to talk

00:26:54 --> 00:26:59

about the fire watch on the next slide. Basically a fire watch is a

00:27:00 --> 00:27:03

is the use of a standby employee equipped with a fire extinguisher,

00:27:04 --> 00:27:09

whose sole job is to monitor for sparks or flames. So they're not

00:27:09 --> 00:27:13

doing anything other than watching for the flame spread or for

00:27:13 --> 00:27:17

sparks. This employee should remain in the area for at least 30

00:27:17 --> 00:27:20

minutes after hot work is complete, to continue monitoring,

00:27:20 --> 00:27:25

especially as I said, in case of welding, the metal itself is still

00:27:25 --> 00:27:30

going to be red hot even after you stop applying the welding material

00:27:30 --> 00:27:33

itself to it. So you're going to keep a watch for another 30

00:27:33 --> 00:27:37

minutes, just to make sure nothing comes in touch with that hot

00:27:37 --> 00:27:40

surface causing it to ignite that material.

00:27:42 --> 00:27:46

I for open fires. The best practice is not to allow open

00:27:46 --> 00:27:50

fires on the job. Some state and county laws prohibit burning

00:27:50 --> 00:27:53

without a permit. So again, to minimize the possibility of

00:27:53 --> 00:27:54

spreading fire.

00:27:56 --> 00:27:59

So that's basically our presentation about fire fire

00:27:59 --> 00:28:03

protection, fire protection devices, their availability, and

00:28:03 --> 00:28:07

so on and so forth. So here are some questions that we need to

00:28:07 --> 00:28:10

know the answers to. What are the four steps used to

00:28:12 --> 00:28:16

for to using a fire extinguisher? Remember the acronym pass P, A, S,

00:28:16 --> 00:28:21

S, so that's the answer to the first question. P is

00:28:23 --> 00:28:24

point,

00:28:25 --> 00:28:33

and then remove the pin. A is aim, S is squeeze, and the other s is

00:28:33 --> 00:28:35

swipe across the base of the flame.

00:28:36 --> 00:28:41

What type fires does a BC extinguisher protect against it's

00:28:41 --> 00:28:45

a BC, so it protects against B and C, and in this case, it's going to

00:28:45 --> 00:28:50

be electrical and fuel, fuel is B and electrical is C.

00:28:51 --> 00:28:54

What should you do before refueling equipment? If you're

00:28:54 --> 00:28:57

going to refuel an equipment for use on a construction site, what

00:28:57 --> 00:29:00

should you do before that? Of course, it's going to be shutting

00:29:00 --> 00:29:04

off that equipment. How many fire extinguishers are required in a

00:29:04 --> 00:29:08

building under construction? We talked about different methods of

00:29:08 --> 00:29:11

calculation. One of them is every

00:29:12 --> 00:29:16

3000 square feet, or at least one per floor, and the access should

00:29:16 --> 00:29:21

not be more than 100 feet in any direction for you to be able to

00:29:21 --> 00:29:25

access that fire safety. So this is our presentation today about

00:29:25 --> 00:29:29

fire safety. I hope you have understood the material and please

00:29:29 --> 00:29:31

stay safe. Thank you. Bye.

Share Page